Delta Busway System - BR Series, 250-2000A


Delta · Data Center · Power Distribution
A Flexible, Safe, and Reliable Low Voltage Power Distribution Solution
Supplied in Israel by Somet Integration, official Delta distributor — sizing, installation, commissioning and service from our team in Lod.
Delta Busway System – BR Series, 250-2000A
A Flexible, Safe, and Reliable Low Voltage Power Distribution Solution
With the brand vision “Smarter, Greener, Together,” Delta has utilized its industry-leading power electronics technology to develop the Busway BR Series for data center applications. Different from a conventional power cable system or sandwich busway solutions, Delta has adopted epoxy cast resin technology to significantly increase IP protection level, safety, and reliability. Delta’s solution is ideal for use in a variety of industries and climate conditions. The superior electrical and mechanical characteristics of resin minimize the Busway BR Series’ dimensions and simplify its structure. The Busway BR Series also has an extended product life cycle, increased reusability, and achieves significant energy savings for customers.
The Busway BR Series features:
Successive plug-in slots are available for expansion and power distribution. Data centers can use them freely
Ultra safe solution that satisfies the requirements of data centers
Conforms to different standards, depending on market or customer needs, such as IEC, CNS and GB
Space-saving and weight-saving solution that overcomes space and loading problems of the data center.
Highly integrated composite materials that significantly reduce EMC and protect precision devices in the data center, and are safe for human health.
Part of the Delta Data Center Infrastructure portfolio · Power Distribution.
| Busway | |
| Rating | 250/ 400/ 600/ 800/ 1000/ 1250/ 1600/ 2000 A |
| Rated voltage | 1000 V |
| Frequency | 50/60 Hz |
| Conductor | Copper purity: 99.9%, conductivity: 99.9% IACS |
| Aluminum purity: 98.8%, conductivity: 56.0% IACS | |
| Conductor plating | Tin plating (Std) |
| Insulation material | Epoxy cast resin |
| Insulation class | Class F (155℃) |
| Enclosure/ housing | Epoxy/ Aluminum |
| Fire protection | UL94 V0 |
| Ingress protection rating | IP20, IP55 (optional) |
| Mechanical Impact | IK10 |
| Earthquake test | 0.8 g [magnitude >7], Zone 4 |
| Plug-in Unit | |
| Contact design | Plug-in type |
| Type | Rv: mounted to busway section vertically |
| Rh: mounted to busway section horizontally | |
| Configuration | Plug-in unit w/ MCB/ELCB/RCBO |
| Plug-in unit w/ MCB/RCB + Socket-outlets | |
| Plug-in unit w/ MCB/RCBO + Power Meter | |
| Plug-in unit w/ MCB + Over Temperature Detect System | |
| Max. Rating | 400 A |
| MCCB brands | ABB(Std.), Mitsubishi, Fuji, GE, Schneider or Customer specified |
| Ingress protection rating | IP20, IP42/55 (optional) |
| Panel coating | Powder coated paint |
| Color | RAL 9011/ RAL9003 |
| General Data | |
| Standards | IEC61439, IEC60529, IEC60331, IEC60332 |
| CNS14286, CNS12514, CNS14165, CNS11073 | |
| UL857 | |
| Ambient temperature | -20℃ /+50℃ avg. 35℃ |
| Altitude | Below 2000 m from sea level |
| COPPER | |
| Model | BRC02 |
| Rated current | 250 A |
| Impedance values* | Resistance R20: 213.0 μΩ/m |
| Resistance R80: 263.2 μΩ/m | |
| Resistance X50: 138.1 μΩ/m | |
| Impedance Z50: 297.2 μΩ/m | |
| Resistance X60: 165.7 μΩ/m | |
| Impedance Z60: 311.0 μΩ/m | |
| Conductor Cross-section Area | L1,L2,L3: 50 mm² |
| N (100%): 50 mm² | |
| G (Internal): 50 mm² | |
| Dimensions (W x H) | 117 x 58 mm |
| Weight | 12 kg/m |
| Model | BRC04 |
| Rated current | 400 A |
| Impedance values* | Resistance R20: 178.0 μΩ/m |
| Resistance R80: 220.0 μΩ/m | |
| Resistance X50: 129.5 μΩ/m | |
| Impedance Z50: 255.3 μΩ/m | |
| Resistance X60: 155.4 μΩ/m | |
| Impedance Z60: 269.3 μΩ/m | |
| Conductor Cross-section Area | L1,L2,L3: 72.5 mm² |
| N (100%): 72.5 mm² | |
| G (Internal): 72.5 mm² | |
| Dimensions (W x H) | 117 x 58 mm |
| Weight | 13 kg/m |
| Model | BRC06 |
| Rated current | 600 A |
| Impedance values* | Resistance R20: 117.8 μΩ/m |
| Resistance R80: 145.6 μΩ/m | |
| Resistance X50: 87.8 μΩ/m | |
| Impedance Z50: 170.0 μΩ/m | |
| Resistance X60: 105.3 μΩ/m | |
| Impedance Z60: 179.7 μΩ/m | |
| Conductor Cross-section Area | L1,L2,L3: 145 mm² |
| N (100%): 145 mm² | |
| G (Internal): 72.5 mm² | |
| Dimensions (W x H) | 117 x 58 mm |
| Weight | 15 kg/m |
| Model | BRC08 |
| Rated current | 800 A |
| Impedance values* | Resistance R20: 74.6 μΩ/m |
| Resistance R80: 92.2 μΩ/m | |
| Resistance X50: 67.8 μΩ/m | |
| Impedance Z50: 114.4 μΩ/m | |
| Resistance X60: 81.3 μΩ/m | |
| Impedance Z60: 122.9 μΩ/m | |
| Conductor Cross-section Area | L1,L2,L3: 232 mm² |
| N (100%): 232 mm² | |
| G (Internal): 116 mm² | |
| Dimensions (W x H) | 117 x 73 mm |
| Weight | 23 kg/m |
| Model | BRC10 |
| Rated current | 1000 A |
| Impedance values* | Resistance R20: 55.8 μΩ/m |
| Resistance R80: 69.0 μΩ/m | |
| Resistance X50: 49.8 μΩ/m | |
| Impedance Z50: 85.1 μΩ/m | |
| Resistance X60: 59.8 μΩ/m | |
| Impedance Z60: 91.3 μΩ/m | |
| Conductor Cross-section Area | L1,L2,L3: 307.4 mm² |
| N (100%): 307.4 mm² | |
| G (Internal): 153.7 mm² | |
| Dimensions (W x H) | 117 x 86 mm |
| Weight | 32 kg/m |
| Model | BRC12 |
| Rated current | 1250 A |
| Impedance values* | Resistance R20: 37.2 μΩ/m |
| Resistance R80: 46.0 μΩ/m | |
| Resistance X50: 38.5 μΩ/m | |
| Impedance Z50: 60.0 μΩ/m | |
| Resistance X60: 46.2 μΩ/m | |
| Impedance Z60: 65.2 μΩ/m | |
| Conductor Cross-section Area | L1,L2,L3: 464 mm² |
| N (100%): 464 mm² | |
| G (Internal): 232 mm² | |
| Dimensions (W x H) | 117 x 113 mm |
| Weight | 46 kg/m |
| Model | BRC16 |
| Rated current | 1600 A |
| Impedance values* | Resistance R20: 24.6 μΩ/m |
| Resistance R80: 30.4 μΩ/m | |
| Resistance X50: 25.5 μΩ/m | |
| Impedance Z50: 39.7 μΩ/m | |
| Resistance X60: 30.6 μΩ/m | |
| Impedance Z60: 43.1 μΩ/m | |
| Conductor Cross-section Area | L1,L2,L3: 696 mm² |
| N (100%): 696 mm² | |
| G (Internal): 348 mm² | |
| Dimensions (W x H) | 117 x 153 mm |
| Weight | 59 kg/m |
| Model | BRC20 |
| Rated current | 2000 A |
| Impedance values* | Resistance R20: 18.8 μΩ/m |
| Resistance R80: 23.2 μΩ/m | |
| Resistance X50: 20.1 μΩ/m | |
| Impedance Z50: 30.7 μΩ/m | |
| Resistance X60: 24.1 μΩ/m | |
| Impedance Z60: 33.5 μΩ/m | |
| Conductor Cross-section Area | L1,L2,L3: 928 mm² |
| N (100%): 928 mm² | |
| G (Internal): 464 mm² | |
| Dimensions (W x H) | 117 x 193 mm |
| Weight | 65 kg/m |
| ALUMINUM | |
| Model | BRA02 |
| Rated current | 250 A |
| Impedance values* | Resistance R20: 312.0 μΩ/m |
| Resistance R80: 385.6 μΩ/m | |
| Resistance X50: 150.0 μΩ/m | |
| Impedance Z50: 413.7 μΩ/m | |
| Resistance X60: 180.0 μΩ/m | |
| Impedance Z60: 425.5 μΩ/m | |
| Conductor Cross-section Area | L1,L2,L3: 100 mm² |
| N (100%): 100 mm² | |
| G (Internal): 50 mm² | |
| Dimensions (W x H) | 117 x 58 mm |
| Weight | 11 kg/m |
| Model | BRA04 |
| Rated current | 400 A |
| Impedance values* | Resistance R20: 213.0 μΩ/m |
| Resistance R80: 263.2 μΩ/m | |
| Resistance X50: 138.1 μΩ/m | |
| Impedance Z50: 297.2 μΩ/m | |
| Resistance X60: 165.7 μΩ/m | |
| Impedance Z60: 311.0 μΩ/m | |
| Conductor Cross-section Area | L1,L2,L3: 145 mm² |
| N (100%): 145 mm² | |
| G (Internal): 72.5 mm² | |
| Dimensions (W x H) | 117 x 58 mm |
| Weight | 12 kg/m |
| Model | BRA06 |
| Rated current | 600 A |
| Impedance values* | Resistance R20: 122.0 μΩ/m |
| Resistance R80: 150.8 μΩ/m | |
| Resistance X50: 100.0 μΩ/m | |
| Impedance Z50: 180.9 μΩ/m | |
| Resistance X60: 120.0 μΩ/m | |
| Impedance Z60: 192.7 μΩ/m | |
| Conductor Cross-section Area | L1,L2,L3: 232 mm² |
| N (100%): 232 mm² | |
| G (Internal): 116 mm² | |
| Dimensions (W x H) | 117 x 73 mm |
| Weight | 14 kg/m |
| Model | BRA08 |
| Rated current | 800 A |
| Impedance values* | Resistance R20: 93.5 μΩ/m |
| Resistance R80: 115.5 μΩ/m | |
| Resistance X50: 59.8 μΩ/m | |
| Impedance Z50: 130.1 μΩ/m | |
| Resistance X60: 71.7 μΩ/m | |
| Impedance Z60: 136.0 μΩ/m | |
| Conductor Cross-section Area | L1,L2,L3: 307.4 mm² |
| N (100%): 307.4 mm² | |
| G (Internal): 153.7 mm² | |
| Dimensions (W x H) | 117 x 86 mm |
| Weight | 21 kg/m |
| Model | BRA10 |
| Rated current | 1000 A |
| Impedance values* | Resistance R20: 62.6 μΩ/m |
| Resistance R80: 77.4 μΩ/m | |
| Resistance X50: 46.7 μΩ/m | |
| Impedance Z50: 90.3 μΩ/m | |
| Resistance X60: 56.0 μΩ/m | |
| Impedance Z60: 95.5 μΩ/m | |
| Conductor Cross-section Area | L1,L2,L3: 464 mm² |
| N (100%): 464 mm² | |
| G (Internal): 232 mm² | |
| Dimensions (W x H) | 117 x 113 mm |
| Weight | 30 kg/m |
| Model | BRA12 |
| Rated current | 1250 A |
| Impedance values* | Resistance R20: 49.7 μΩ/m |
| Resistance R80: 61.4 μΩ/m | |
| Resistance X50: 40.8 μΩ/m | |
| Impedance Z50: 73.8 μΩ/m | |
| Resistance X60: 49.0 μΩ/m | |
| Impedance Z60: 78.6 μΩ/m | |
| Conductor Cross-section Area | L1,L2,L3: 580 mm² |
| N (100%): 580 mm² | |
| G (Internal): 290 mm² | |
| Dimensions (W x H) | 117 x 133 mm |
| Weight | 42 kg/m |
| Model | BRA16 |
| Rated current | 1600 A |
| Impedance values* | Resistance R20: 41.8 μΩ/m |
| Resistance R80: 51.7 μΩ/m | |
| Resistance X50: 32.7 μΩ/m | |
| Impedance Z50: 61.1 μΩ/m | |
| Resistance X60: 39.2 μΩ/m | |
| Impedance Z60: 64.8 μΩ/m | |
| Conductor Cross-section Area | L1,L2,L3: 928 mm² |
| N (100%): 928 mm² | |
| G (Internal): 464 mm² | |
| Dimensions (W x H) | 117 x 193 mm |
| Weight | 55 kg/m |
| Model | BRA20 |
| Rated current | 2000 A |
| Impedance values* | Resistance R20: 25.4 μΩ/m |
| Resistance R80: 31.4 μΩ/m | |
| Resistance X50: 19.0 μΩ/m | |
| Impedance Z50: 36.7 μΩ/m | |
| Resistance X60: 22.8 μΩ/m | |
| Impedance Z60: 38.8 μΩ/m | |
| Conductor Cross-section Area | L1,L2,L3: 1160 mm² |
| N (100%): 1160 mm² | |
| G (Internal): 580 mm² | |
| Dimensions (W x H) | 117 x 233 mm |
| Weight | 59 kg/m |
| Rating | 16 A |
| Model | Rv-A3P16 |
| Dimensions (H x D x W) | 330 x 165 x 100 mm |
| IP Rating | IP42 |
| Weight | 3 kg |
| Rating | 32 A |
| Model | Rv-A3P32 |
| Dimensions (H x D x W) | 330 x 165 x 100 mm |
| IP Rating | IP42 |
| Weight | 3 kg |
| Rating | 63 A |
| Model | Rv-A3P63 |
| Dimensions (H x D x W) | 330 x 165 x 100 mm |
| IP Rating | IP42 |
| Weight | 5 kg |
| Rating | 125 A |
| Model | Rv-A3P125 |
| Dimensions (H x D x W) | 330 x 165 x 200 mm |
| IP Rating | IP42 |
| Weight | 12 kg |
| Rating | 250 A |
| Model | Rv-A3P250 |
| Dimensions (H x D x W) | 330 x 165 x 300 mm |
| IP Rating | IP42 |
| Weight | 20 kg |
| Rating | 400 A |
| Model | Rv-A3P400 |
| Dimensions (H x D x W) | 330 x 165 x 300 mm |
| IP Rating | IP42 |
| Weight | 26 kg |
| Rating | 16 A |
| Model | Rh-A3P16 |
| Dimensions (H x D x W) | 250 x 243 x 100 mm |
| IP Rating | IP42 |
| Weight | 3 kg |
| Ratin | 32 A |
| Model | Rh-A3P32 |
| Dimensions (H x D x W) | 250 x 243 x 100 mm |
| IP Rating | IP42 |
| Weight | 3 kg |
| Rating | 63 A |
| Model | Rh-A3P63 |
| Dimensions (H x D x W) | 250 x 243 x 100 mm |
| IP Rating | IP42 |
| Weight | 5 kg |
| Rating | 125 A |
| Model | Rh-A3P125 |
| Dimensions (H x D x W) | 250 x 243 x 200 mm |
| IP Rating | IP42 |
| Weight | 12 kg |
| Rating | 250 A |
| Model | Rh-A3P250 |
| Dimensions (H x D x W) | 250 x 243 x 300 mm |
| IP Rating | IP42 |
| Weight | 20 kg |
| Rating | 400 A |
| Model | Rh-A3P400 |
| Dimensions (H x D x W) | 250 x 243 x 300 mm |
| IP Rating | IP42 |
| Weight | 26 kg |
| Rating | 250 A |
| Model | ECM-250 MCCB / ECT-250 Terminal |
| Dimensions (W x H x D) | ECM-250 MCCB: 480 x 300 x 240 mm |
| ECT-250 Terminal: 430 x 300 x 160 mm | |
| IP Rating | IP42 |
| Weight | ECM-250 MCCB: 17 kg |
| ECT-250 Terminal: 15 kg | |
| Rating | 400 A |
| Model | ECM-400 MCCB / ECT-400 Terminal |
| Dimensions (W x H x D) | ECM-400 MCCB: 480 x 300 x 240 mm |
| ECT-400 Terminal: 430 x 300 x 160 mm | |
| IP Rating | IP42 |
| Weight | ECM-400 MCCB: 19 kg |
| ECT-400 Terminal: 15 kg | |
| Rating | 630 A |
| Model | ECM-630 MCCB / ECT-630 Terminal |
| Dimensions (W x H x D) | ECM-630 MCCB: 480 x 300 x 240 mm |
| ECT-630 Terminal: 430 x 300 x 160 mm | |
| IP Rating | IP42 |
| Weight | ECM-630 MCCB: 20 kg |
| ECT-630 Terminal: 17 kg | |
| Rating | 800 A |
| Model | BRC086EB Terminal |
| Dimensions (W x H x D) | 500 x 650 x 220 mm |
| IP Rating | IP42 |
| Weight | 35 kg |
| Rating | 1000 A |
| Model | BRC106EB Terminal |
| Dimensions (W x H x D) | 500 x 650 x 233 mm |
| IP Rating | IP42 |
| Weight | 38 kg |
| Rating | 1250 A |
| Model | BRC126EB Terminal |
| Dimensions (W x H x D) | 500 x 650 x 260 mm |
| IP Rating | IP42 |
| Weight | 45 kg |
| Rating | 1600 A |
| Model | BRC166EB Terminal |
| Dimensions (W x H x D) | 500 x 650 x 300 mm |
| IP Rating | IP42 |
| Weight | 55 kg |
| Rating | 2000 A |
| Model | BRC206EB Terminal |
| Dimensions (W x H x D) | 500 x 650 x 340 mm |
| IP Rating | IP42 |
| Weight | 65 kg |
Specifications per Delta Electronics; subject to change without prior notice. Contact Somet Integration to confirm the exact configuration for your project.
- Product available regions : EMEA North America Latin America SEA & OCEA India China Taiwan South Korea Japan ● 250-1600A ● ● ● ● ● ● ● For region-specific product details and variations in specifications, please download the local leaflet or visit the local website.
Downloads
- Delta Busway System – BR Series, 250-2000A – datasheet (PDF)
- Busway System – BR Series, 250-1600A, UL (Brochure) : for North America
Buy & Support
Somet Integration is the official distributor of Delta Electronics critical-infrastructure products in Israel. We provide project sizing, quotations, delivery, installation, commissioning, maintenance contracts and battery replacement.
Request a quote
Get local pricing, availability, sizing and installation for the Delta Busway System – BR Series, 250-2000A from Somet Integration.
Prefer to talk? Call 1-700-700-193, email somet@sometltd.com or message us on WhatsApp.