VT408D Sensor extension unit




Vutlan · Sensors
The VT408D Extension unit increases the number of analog sensors connected to any Vutlan monitoring device.
- Inputs: 8 analog sensor ports, RJ11 6P4C CAN ports
- Max. bus length: 225m,
- Max. length of analog sensor cables: 50-150m (depends on sensor type)
- Power input: 12V DC
- Connects to the Vutlan CAN bus — daisy-chain with other CAN devices
- Up to 225 m from the monitoring unit
Available in Israel exclusively through Somet Integration — local stock, pricing, project design, installation support and warranty.
VT408D Sensor extension unit
The VT408D Extension unit increases the number of analog sensors connected to any Vutlan monitoring device.
All connected sensors are automatically detected and integrated into the system. CAN devices can be connected in a chain.
DIN mounting.
Key features
- Inputs: 8 analog sensor ports, RJ11 6P4C CAN ports
- Max. bus length: 225m,
- Max. length of analog sensor cables: 50-150m (depends on sensor type)
- Power input: 12V DC
- Mounting possibilities: DIN rail 7mm depth, 15mm depth
- Connects to the Vutlan CAN bus — daisy-chain with other CAN devices
- Up to 225 m from the monitoring unit
- Made in EU
| Device type | CAN bus device |
| Network Interface | CAN open |
| Inputs | 8 analog sensor ports, RJ11 6P4C CAN ports |
| Daisy chain | Yes, can be connected in a chain with other CAN bus sensors and extensions. |
| Operating temperature | -10° C to +80° C |
| Max. bus length | 225m, |
| Max. length of analog sensor cables | 50-150m (depends on sensor type) |
| Maximum units in a chain | You can install a maximum of 10 units, provided that no other CAN devices are installed in a CAN chain. |
| Power input | 12V DC |
| Dimensions | Width 129, Height 28.6, Depth 56 mm |
| Mounting possibilities | DIN rail 7mm depth, 15mm depth |
| Status Indicators | Red (Error) / Green Led (Run) |
| TR switch | Activate if the unit is the last unit in a CAN bus chain. |
| Origin of goods | Made in EU |
| HS Code | 8471 50 000 |
| GTIN | 8588009886464 You can connect multiple CAN devices to a CAN bus chain. Each VT408 unit in the CAN bus chain adds 8 analog sensors. Each VT440 unit adds 32 or 64 dry contact inputs to the system. An additional CAN12V-1A power supply is only |
| Systems with CAN ports | To read data from the CAN sensors, you need a Vutlan monitoring device with one or two CAN ports. |
Recommended Vutlan products to use with this item:
Request a quote
Somet Integration is the exclusive distributor of Vutlan in Israel. Get local pricing, stock availability, project design and technical support for the VT408D.
Prefer to talk? Call 1-700-700-193, email somet@sometltd.com or message us on WhatsApp.