Delta D50 – Rear Door Heat Exchanger (RDHx)


Delta · Data Center · Cooling
Delta CoolDoor is the ideal solution for high-power-density racks.
- Cooling Capacity: 50 kW(2)
- Rated Air Flow: 4016 CFM
- Net Weight: 98 kg
- Maximum CW Flow Rate: 122 LPM (PICV 108 LPM)
- Built-in MCU precisely controls water and air flow for accurate temperature management
Supplied in Israel by Somet Integration, official Delta distributor — sizing, installation, commissioning and service from our team in Lod.
Delta D50 – Rear Door Heat Exchanger (RDHx)
Delta CoolDoor is the ideal solution for high-power-density racks. With EC fans ensuring reliability and efficiency, it removes heat at the source, preventing hot air in the room. No need for added footprint or raised floor, the CoolDoor saves space and reduces CAPEX. The turbo boost dissipates heat from neighboring racks, and the leakage detection ensures high reliability. Elevate your data center performance with Delta CoolDoor!
The D50 is part of the Delta Rear Door Heat Exchanger (RDHx), CoolDoor 30/50 kW range (Cooling). See all Delta Data Center Infrastructure.
| Model | D50 |
| Cooling Capacity | |
| Cooling Capacity | 50 kW(2) |
| Rated Air Flow | |
| Rated Air Flow | 4016 CFM |
| Physical | |
| Compatible Rack Heights | 42-60U |
| Compatible Rack Widths | 600-800 mm |
| Dimensions (W x D x H) | 600 x 345 x 1970 mm |
| Net Weight | |
| Net Weight | 98 kg |
| Deployment | |
| Inlet Chiller Water Temperature | 12°C (recommended) to 20°C(3) |
| Inlet chiller water temperature should be higher than dew point temperature | |
| Maximum Operating Pressure | 10 bar (145 psi) |
| Maximum CW Flow Rate | |
| Maximum CW Flow Rate | 122 LPM (PICV 108 LPM) |
| Rated Water Flow | |
| Rated Water Flow | 90 LPM |
| Piping Connection | Top/Bottom |
| Piping Size | |
| Piping Size | 1 1/4 inch |
| Power Supply | |
| Nominal Voltage | 200/208/220/230/240 Vac, 1P2W+PE |
| Frequency | 50/60 Hz |
| Input Connection Type | NEMA 6-15P |
| Rated Power Consumption | |
| Rated Power Consumption | 0.67 kW |
| Power Feed Location | Top |
| Mechanical | |
| Valve Type | 2-way valve, FC type |
| Fan Type | EC |
| Fan Quantity | 4 |
| Water Leakage Detector | 4m length |
| Communication Interface | |
| Display | LCD display with LED indicators |
| Port | Modbus RTU (RS-485), Remote On/Off input dry contact, Fire alarm input dry contact, Total alarm output dry contact |
| Conformance | |
| Safety | CE, UL(4) |
| Features | |
| Leak Detection | Standard |
| Dual Power Feeds | Optional |
| Cut-off Valve (Isolate Leakage RDHx) | Optional |
| T/RH Sensor-Cold Side Dew Point Monitoring | Optional |
| PICV Valve | Optional |
| Air Static Pressure Sensor | Optional |
| Quick Disconnect Couplings | Optional |
| BACnet | Optional |
| SNMP Card | Optional |
Specifications per Delta Electronics; subject to change without prior notice. Contact Somet Integration to confirm the exact configuration for your project.
Unparalleled Reliability
- Built-in MCU precisely controls water and air flow for accurate temperature management
- Ensures chiller system stability during power recovery with a two-way ball valve design post-emergency shutdown
- Turbo boost control ensures uninterrupted operation by utilizing adjacent RDHx during ball valve or fan failure
- Enhances equipment protection with 4m water leakage detection and integrated cut-off valve (option) to minimize potential damage
- Integrated ATS (optional) for continuous operation
- Elevates security with lockable access door
Efficient Use of Space and Energy
- No hot aisle containment needed
- Low profile design mounts seamlessly on the rear of the rack, saving valuable space
- Enhance energy savings with an adjustable fan speed (30-100%) and high-efficiency EC fan
Easy Management
- LCD screen and LED indicators for onsite monitoring system status and control
- Empowers remote monitoring through input dry contact and external RTU device
- Tailor-made ducts, perfect for all rack types
- Hot-swappable fans and sensors allow for quick and easy maintenance
- Flow control valve (optional) delivers high cooling availability and control
- Product available regions : EMEA North America Latin America SEA & OCEA India China Taiwan South Korea Japan ● ● ● ● For region-specific product details and variations in specifications, please download the local leaflet or visit the local website.
Downloads
- Delta D50 – Rear Door Heat Exchanger (RDHx) – datasheet (PDF)
- Rear Door Heat Exchanger, CoolDoor 30/50 kW (User Manual)
Buy & Support
Somet Integration is the official distributor of Delta Electronics critical-infrastructure products in Israel. We provide project sizing, quotations, delivery, installation, commissioning, maintenance contracts and battery replacement.
Request a quote
Get local pricing, availability, sizing and installation for the Delta D50 – Rear Door Heat Exchanger (RDHx) from Somet Integration.
Prefer to talk? Call 1-700-700-193, email somet@sometltd.com or message us on WhatsApp.